If you run into a situation where a valve or auxilary circuit on your Pentair pool controller no longer functions at all, don't despair! Assuming the required electrical connections are good, the fault isn't caused by a programming error, and you're trying to control the valve or aux circuit at the outdoor panel (and not using screenlogic or a remote), you may just have a blown relay driver chip... these are cheap and easy to replace. Aux circuits AND valves are actually controlled by relays which are either on-board, or in the load center. The aux relays are the large-ish 2" x 1.25" Omron devices that are bolted to the load center/enclosure, while the valve relays are the smaller .5 x .25" relays that are soldered onto the outdoor control board (or personality board for Intellitouch). Valve relays on an Intellitouch personality board They're all 24vdc relays, which means 24 volts dc is required to "energize" their coils. The micro-c...